SDS8C LDC |
SDS16C LDC |
SDS32C LDC |
| Processor |
MPC8349E, 400 Mhz, 750 MIPS |
| Memory |
| RAM MB |
64 |
64 |
64 |
| Flash MB |
16 |
16 |
16 |
| Interface Ports |
| Number of Serial Ports |
8 |
16 |
32 |
| Serial Port Interface |
Software selectable RS232 / RS485 / RS422 DTE on RJ45 - RS485: full and half duplex |
| Sun / Solaris |
Sun / Oracle ‘Solaris' Safe - no "break signal" sent during power cycle causing costly server re-boots or downtime |
| Serial Port Speeds |
50bps to 230Kbps with customizable baud rate support |
| Data Bits |
5,6,7,8, 9-bit protocol support |
| Parity |
Odd, Even, Mark, Space, None |
| Flow Control |
Hardware, Software, Both, None |
| Local Console Port |
RS232 on RJ45 with DB9 adapter ( provided ) |
| Network |
Dual 10/100/1000-base TX Ethernet RJ45 |
| Software selectable Ethernet speed 10/100/1000, Auto |
| Software selectable Half/Full/Auto duplex |
| Failsafe Alarm Relay |
3A@24v DC. Normally open contacts closed by IOLAN when active and opened upon alarm condition or power failure |
| Power |
| Dual Power Supply |
2 x Pluggable Terminal Blocks with screw terminals accommodating 28 - 12 AWG wire sizes |
| Nominal Input Voltage |
24v DC / 48v DC |
| Input Voltage Range |
18 - 72v DC |
| Current Consumption @ 18v DC (Amps) |
0.4 |
0.55 |
0.85 |
| Current Consumption @ 24v DC (Amps) |
0.3 |
0.4 |
0.65 |
| Current Consumption @ 48v DC (Amps) |
0.2 |
0.25 |
0.35 |
| Current Consumption @ 72v DC (Amps) |
0.15 |
0.18 |
0.25 |
| Typical Power Consumption (Watts) |
11 |
13 |
18 |
| Chassis Ground |
Grounding screw for a #10 ring terminal |
| Indicators |
| LEDs |
Power |
| System Ready |
| Network Link activity |
| Serial: Transmit and Receive data per port |
| Environmental Specifications |
| Heat Output ( BTU/HR ) |
37.6 |
44.4 |
61.5 |
| MTBF ( Hours )* |
126,302 |
105,495 |
82,402 |
| Operating Temperature |
-40C ambient for 16 hours and +70C ambient for 16 hours without use of fans |
| Storage Temperature |
-40C to 85C, -40F to 185F |
| Humidity |
5 to 95% (non condensing) for both storage and operation. |
| Case |
SECC Zinc plated sheet metal (1 mm) |
| Ingress Protection Rating |
IP30 |
| Mounting |
1U - 19" rack, front and rear mounting hardware included. DIN Rail mounting kit optional |
| Product Weight and Dimensions |
| Weight |
3.16 kg |
3.18 kg |
3.36 kg |
| Dimensions |
1U Rack form factor - 26.4 x 43.4 x 4.4 (cm), 10.38 x 17.1 x 1.75 (in) |
| Packaging |
| Shipping Weight |
3.96 kg |
3.98 kg |
4.16 kg |
| Shipping Dimensions |
59 x 36 x 9 (cm), 23 x 14 x 3.5 (in) |
| Regulatory Approvals |
| Network Equipment Building Systems ( NEBS ) |
SR-3580 NEBS Level 3 |
| GR-1089-CORE : NEBS EMI and Safety |
| GR-1089-CORE per Verizon VZ.TPR.9205 and ATT-TP-76200 |
| GR-63-CORE: NEBS Physical Protection |
| GR-63-CORE / ANSI T1.319 per Verizon VZ.TPR.9305 and ATT-TP-76200 |
| Emissions |
Power Line conducted: IEC 61850-3 Sec 5.8 |
| CISPR 32:2015/EN 55032:2015 (Class A) |
| EN55011 (CISPR11) |
| Telecom Line conducted: IEC 61000-6-4 |
| Radiated: IEC 61850-3 Sec 5.8 |
| CISPR 24:2010/EN 55024:2010 |
| EN61000-3-2 : 2010 Limits for Harmonic Current Emissions |
| EN61000-3-3 : 2010, Limits of Voltage Fluctuations and Flicker |
| EMC Interface Immunity |
IEC 61850-3 ( substations ) IEEE 1613 ( substations ) (C37.90.x ) Applies to all ports, signal and power connections |
| ESD: IEC61000-4-2, 8Kv Contact / 15Kv Air |
| Radiated RFI: IEC61000-4-3, 20 V/m ( 80M-1G ) |
| Fast Transients / Burst: IEC61000-4-4, 4Kv Mains , I/O |
Surge : IEC61000-4-5 4Kv AC line to Gnd, 2Kv AC Line to Line, 2Kv DC line to Gnd, 1 Kv DC Line to Line, RS232 = balanced, ethernet = unbalanced |
| Conducted RF: IEC61000-4-6, 10 Vrms |
| Magnetic Field: IEC61000-4-8, 100 A/m, 1000 A/m (1 sec) |
| Dips and Interrupts: IEC61000-4-11, Criteria A/B/C |
| Oscillatory: EN61000-4-12, 2.5Kv common and differential mode |
| Low Frequency conducted: EN61000-4-16, 30V 60s, 300V 1s,15Hz-150KHz @ level 3 |