TRIO-PS-2G/3AC/24DC/5 - 29031538 |
TRIO-PS-2G/3AC/24DC/10 - 29031548 |
TRIO-PS-2G/3AC/24DC/20 - 29031558 |
TRIO-PS-2G/3AC/24DC/40 - 29031568 |
General |
Net weight |
0.4 kg |
0.9 kg |
1.5 kg |
2.6 kg |
Efficiency |
> 91 % (at 400 V AC and nominal values) |
> 92 % (at 400 V AC and nominal values) |
> 93 % (400 V AC) |
typ. 93 % (400 V AC) |
Insulation voltage input/output |
3 kV AC (type test) |
3 kV AC (type test) |
3 kV AC (type test) |
3 kV AC (type test) |
|
1.5 kV AC (routine test) |
1.5 kV AC (routine test) |
1.5 kV AC (routine test) |
1.5 kV AC (routine test) |
Degree of protection |
IP20 |
IP20 |
IP20 |
IP20 |
MTBF (IEC 61709, SN 29500) |
> 2300000 h (25 °C) |
> 2100000 h (25 °C) |
> 1800000 h (25 °C) |
> 1730000 h (25 °C) |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
horizontal DIN rail NS 35, EN 60715 |
horizontal DIN rail NS 35, EN 60715 |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
Efficiency |
|
|
500 V AC |
typ. 93.3 % (480 V AC) |
Standards and Regulations |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Conformance with EMC Directive 2014/30/EU |
Conformance with EMC Directive 2014/30/EU |
Conformance with EMC Directive 2014/30/EU |
Noise emission |
EN 55011 (EN 55022) |
EN 55011 (EN 55022) |
EN 55011 (EN 55022) |
EN 55011 (EN 55022) |
Noise immunity |
Immunity according to EN 61000-6-2 (industrial) |
Immunity according to EN 61000-6-2 (industrial) |
Immunity according to EN 61000-6-2 (industrial) |
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial) |
Standards/regulations |
EN 61000-4-2 |
EN 61000-4-2 |
EN 61000-4-2 |
EN 61000-4-2 |
Contact discharge |
4 kV (Test Level 2) |
4 kV (Test Level 2) |
4 kV (Test Level 2) |
4 kV (Test Level 2) |
Standards/regulations |
EN 61000-4-3 |
EN 61000-4-3 |
EN 61000-4-3 |
EN 61000-4-3 |
Frequency range |
80 MHz ... 1 GHz |
80 MHz ... 1 GHz |
80 MHz ... 1 GHz |
80 MHz ... 1 GHz |
Test field strength |
10 V/m (Test Level 3) |
10 V/m (Test Level 3) |
10 V/m (Test Level 3) |
10 V/m (Test Level 3) |
Frequency range |
1.4 GHz ... 2 GHz |
1.4 GHz ... 2 GHz |
1.4 GHz ... 2 GHz |
1.4 GHz ... 2 GHz |
Test field strength |
3 V/m (Test Level 2) |
3 V/m (Test Level 2) |
3 V/m (Test Level 2) |
3 V/m (Test Level 2) |
Standards/regulations |
EN 61000-4-4 |
EN 61000-4-4 |
EN 61000-4-4 |
EN 61000-4-4 |
Comments |
Criterion B |
Criterion B |
Criterion B |
Criterion B |
Standards/regulations |
EN 61000-6-3 |
EN 61000-6-3 |
EN 61000-6-3 |
EN 61000-6-3 |
Frequency range |
0.15 MHz ... 80 MHz |
0.15 MHz ... 80 MHz |
0.15 MHz ... 80 MHz |
0.15 MHz ... 80 MHz |
Voltage |
10 V (Test Level 3) |
10 V (Test Level 3) |
10 V (Test Level 3) |
10 V (Test Level 3) |
Conducted noise emission |
EN 55016 EN 61000-6-4 (Class A) |
EN 55016 EN 61000-6-4 (Class A) |
EN 55016 EN 61000-6-4 (Class A) |
EN 55016 EN 61000-6-4 (Class A) |
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
Conformance with Low Voltage Directive 2014/35/EC |
Conformance with Low Voltage Directive 2014/35/EC |
Conformance with Low Voltage Directive 2014/35/EC |
Standard - Safety of transformers |
EN 61558-2-16 (air clearances and creepage distances only) |
EN 61558-2-16 (air clearances and creepage distances only) |
EN 61558-2-16 (air clearances and creepage distances only) |
|
Standard - Electrical safety |
IEC 60950-1/VDE 0805 (SELV) |
IEC 60950-1/VDE 0805 (SELV) |
IEC 60950-1/VDE 0805 (SELV) |
IEC 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
EN 50178/VDE 0160 (PELV) |
EN 50178/VDE 0160 (PELV) |
EN 50178/VDE 0160 (PELV) |
Input data |
Nominal input voltage range |
3x 400 V AC ... 500 V AC |
3x 400 V AC ... 500 V AC |
3x 400 V AC ... 500 V AC |
3x 400 V AC ... 500 V AC |
|
2x 400 V AC ... 500 V AC |
2x 400 V AC ... 500 V AC |
2x 400 V AC ... 500 V AC |
|
Input voltage range |
3x 400 V AC ... 500 V AC -20 % ....+15 % |
3x 400 V AC ... 500 V AC -20 % ....+15 % |
3x 400 V AC ... 500 V AC -20 % ....+15 % |
3x 400 V AC ... 500 V AC -20 % ....+15 % |
AC frequency range |
50 Hz ... 60 Hz |
50 Hz ... 60 Hz |
50 Hz ... 60 Hz |
50 Hz ... 60 Hz |
Discharge current to PE |
< 0.25 mA |
< 3.5 mA |
< 3.5 mA |
< 3.5 mA |
Current consumption |
3x 0.4 A (400 V AC) |
3x 0.6 A (400 V AC) |
3x 1.2 A (400 V AC) |
3x 1.9 A (400 V AC) |
Nominal power consumption |
243.6 VA |
451.7 VA |
822.2 VA |
1335.1 VA |
Inrush surge current |
≤ 22 A (typical) |
≤ 26 A (typical) |
≤ 22 A (typical) |
≤ (typical) |
Mains buffering |
typ. 20 ms (400 V AC) |
typ. 10 ms (400 V AC) |
typ. 10 ms (400 V AC) |
typ. 10 ms (400 V AC) |
Input fuse |
3.15 A (internal (device protection), slow-blow) |
3.15 A (internal (device protection), slow-blow) |
3.15 A (internal (device protection), slow-blow) |
6.3 A (internal (device protection)) |