Environmental Product Compliance |
REACH SVHC |
Lead 7439-92-1 |
China RoHS |
Environmentally Friendly Use Period = 25; |
General |
Net weight |
0.3 kg |
Efficiency |
> 90 % |
Insulation voltage input/output |
8 kV DC (type test) |
|
3 kV DC (routine test) |
Protection class |
II |
Degree of protection |
IP20 |
MTBF (IEC 61709, SN 29500) |
> 1160000 h (40 °C) |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: 0 mm horizontally, 30 mm vertically |
Standards and Regulations |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Noise immunity |
EN 61000-6-2:2005 |
Standards/regulations |
EN 61000-4-2 |
Contact discharge |
4 kV (Test Level 3) |
Standards/regulations |
EN 61000-4-3 |
Frequency range |
80 MHz ... 1 GHz |
Test field strength |
10 V/m |
Frequency range |
1.4 GHz ... 2 GHz |
Test field strength |
3 V/m |
Standards/regulations |
EN 61000-4-4 |
Comments |
Criterion B |
Standards/regulations |
EN 61000-6-3 |
|
EN 61000-4-6 |
Frequency range |
10 kHz ... 80 MHz |
Voltage |
10 V (Test Level 3) |
Standards/regulations |
EN 61000-4-11 |
Low Voltage Directive |
Conformance with LV directive 2006/95/EC |
Standard - |
IEC 62109-1 |
Standard - Electrical safety |
IEC 62109-1 |
Standard – Safety extra-low voltage |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
Standard - Safe isolation |
DIN VDE 0100-410 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
UL approvals |
UL 1741 |
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
|
15 Hz ... 150 Hz, 2.3g, 90 min. |
Approval - requirement of the semiconductor industry with regard to mains voltage dips |
EN 61000-4-11 |
Information technology equipment - safety (CB scheme) |
CB Scheme |
Overvoltage category (IEC 62109-1) |
II |
Connection data, input |
Connection method |
Screw connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
14 |
Stripping length |
8 mm |
Screw thread |
M3 |
Output data |
Nominal output voltage |
24 V DC ±1 % |
Nominal output current (IN) |
2.5 A (-25 °C ... 55 °C) |
Derating |
55 °C ... 70 °C (2.5%/K) |
Connection in parallel |
Yes, for redundancy and increased capacity |
Connection in series |
No |
Feedback resistance |
< 35 V DC |
Protection against surge voltage on the output |
≤ 35 V DC |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
|
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
< 20 mVPP (with nominal values) |
Output power |
60 W |
Typical response time |
< 1 s |
Maximum power dissipation in no-load condition |
< 0.5 W |
Power loss nominal load max. |
< 6.5 W |
Dimensions |
Width |
55 mm |
Height |
90 mm |
Depth |
84 mm |
Weight per piece |
316.9 GRM |
Input data |
Nominal input voltage range |
350 V DC ... 900 V DC |
Input voltage range |
300 V DC ... 1000 V DC |
Dielectric strength maximum |
≤ 1050 V DC |
Current consumption |
0.19 A (350 V DC) |
|
0.07 A (1000 V DC) |
Inrush surge current |
< 1 A (typical) |
Choice of suitable circuit breakers |
1 A (Characteristic gPV or comparable) |
Connection data, onput |
Connection method |
Screw connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
14 |
Stripping length |
8 mm |
Screw thread |
M3 |
Ambient conditions |
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C ... 70 °C (> 55° C derating : 2.5%/K) |
Ambient temperature (start-up type tested) |
-40 °C |
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Climatic class |
3K3 (in acc. with EN 60721) |
Degree of pollution |
2 |