Environmental Product Compliance |
REACH SVHC |
Lead 7439-92-1 |
China RoHS |
Environmentally Friendly Use Period = 25; |
General |
Net weight |
0.32 kg |
Efficiency |
typ. 89 % (400 V AC) |
|
typ. 89 % (480 V AC) |
Insulation voltage input/output |
4 kV AC (type test) |
|
3 kV AC (routine test) |
Protection class |
II (in closed control cabinet) |
Degree of protection |
IP20 |
MTBF (IEC 61709, SN 29500) |
828172 h (40 °C) |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: 0 mm horizontally, 30 mm vertically |
Standards and Regulations |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Noise immunity |
EN 61000-6-2:2005 |
Connection in acc. with standard |
CUL |
Standards/regulations |
EN 61000-4-2 |
Contact discharge |
4 kV (Test Level 2) |
Standards/regulations |
EN 61000-4-3 |
Frequency range |
80 MHz ... 1 GHz |
Test field strength |
10 V/m |
Frequency range |
1.4 GHz ... 2 GHz |
Test field strength |
3 V/m |
Standards/regulations |
EN 61000-4-4 |
Comments |
Criterion B |
Standards/regulations |
EN 61000-6-3 |
|
EN 61000-4-6 |
Frequency range |
10 kHz ... 80 MHz |
Voltage |
10 V (Test Level 3) |
Standards/regulations |
EN 61000-4-11 |
Low Voltage Directive |
Conformance with LV directive 2006/95/EC |
Standard - Safety of transformers |
EN 61558-2-16 |
Standard - Electrical safety |
IEC 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage |
IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
Standard - Safe isolation |
DIN VDE 0100-410 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
UL approvals |
UL/C-UL listed UL 508 |
|
UL/C-UL Recognized UL 60950-1 |
|
NEC Class 2 as per UL 1310 |
|
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
|
15 Hz ... 150 Hz, 2.3g, 90 min. |
Approval - requirement of the semiconductor industry with regard to mains voltage dips |
EN 61000-4-11 |
Information technology equipment - safety (CB scheme) |
CB Scheme |
|
Output data |
Nominal output voltage |
24 V DC ±1 % |
Nominal output current (IN) |
3.75 A |
|
3.38 A (Derating 10 %) |
Derating |
55 °C ... 70 °C (2.5%/K) |
Connection in parallel |
no |
Connection in series |
No |
Feedback resistance |
< 35 V DC |
Protection against surge voltage on the output |
≤ 35 V DC |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
|
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
< 50 mVPP (with nominal values) |
Output power |
90 W |
Maximum power dissipation in no-load condition |
< 0.7 W |
Power loss nominal load max. |
< 12 W |
Dimensions |
Width |
55 mm |
Height |
90 mm |
Depth |
84 mm |
Weight per piece |
352.5 GRM |
Input data |
Nominal input voltage range |
2x 400 V AC ... 500 V AC |
Input voltage range |
2x 264 V AC ... 575 V AC |
Current consumption |
0.55 A (400 V AC) |
|
0.48 A (500 V AC) |
Nominal power consumption |
211.3 VA |
Inrush surge current |
< 30 A (typical) |
Mains buffering |
typ. 65 ms (400 V AC) |
|
typ. 100 ms (500 V AC) |
Input fuse |
2 A (slow-blow, internal) |
Choice of suitable circuit breakers |
6 A ... 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) |
0.48 |
Type of protection |
Transient surge protection |
Protective circuit/component |
Varistor |
|
Ambient conditions |
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Climatic class |
3K3 (in acc. with EN 60721) |
Degree of pollution |
2 |