PP-RJ-RJ-F 27030208 |
PP-RJ-SC-F 27030218 |
PP-RJ-SCC-F 27030228 |
PP-RJ-IDC-F 27030238 |
Serial interface |
Interface 1 |
Ethernet interface, 10/100/1000Base-T(X) according to IEEE 802.3u |
Connection method |
RJ45 socket |
Screw terminal block |
Push-in connection |
IDC connection |
Transmission length |
100 m (including patch cables) |
Pin assignment |
1:1 |
Serial transmission speed |
10/100/1000 Mbps |
Maximum output current |
725 mA (PoE) |
Current carrying capacity |
≤ 1.5 A (≤ 60 W (PoE+)) |
Maximum output power |
60 W |
Interface 2 |
Ethernet interface, 10/100/1000Base-T(X) according to IEEE 802.3u |
Connection method |
RJ45 CAT5e |
Conductor cross section solid min. |
|
0.14 mm² |
0.2 mm² |
0.14 mm² |
Conductor cross section solid max. |
|
1.5 mm² |
0.34 mm² |
Conductor cross section flexible min. |
|
0.14 mm² |
0.2 mm² |
0.14 mm² |
Conductor cross section flexible max. |
|
1.5 mm² |
0.34 mm² |
Conductor cross section AWG min. |
|
28 |
26 |
Conductor cross section AWG max. |
|
16 |
22 |
Torque |
|
0.22 Nm ... 0.25 Nm |
|
Stripping length |
|
5 mm |
8 mm |
|
Wire diameter incl. insulation |
|
1.6 mm (Terminal block is tested with PVC insulation - other insulation materials available on request) |
Ambient conditions |
Ambient temperature (operation) |
-40°C ... 75°C |
Ambient temperature (storage/transport) |
-40°C ... 85°C |
Permissible humidity (operation) |
10 % ... 95 % (non-condensing) |
Altitude |
5000 m (For restrictions see manufacturer's declaration) / 2000 m (ATEX approval) |
Degree of protection |
IP20 (Manufacturer's declaration) |
General |
Electrical isolation |
FE // Ethernet |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Net weight |
124.2 g |
Housing material |
Plastic |
Color |
Gray |
MTTF |
3281 Years (SN 29500 standard, temperature 25 °C, operating cycle 21 % (5 days a week, 8 hours a day)) |
3268 Years (SN 29500 standard, temperature 25 °C, operating cycle 21 % (5 days a week, 8 hours a day)) |
3281 Years (SN 29500 standard, temperature 25 °C, operating cycle 21 % (5 days a week, 8 hours a day)) |
1245 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25 % (5 days a week, 12 hours a day)) |
1238 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25 % (5 days a week, 12 hours a day)) |
1245 Years (SN 29500 standard, temperature 40 °C, operating cycle 34.25 % (5 days a week, 12 hours a day)) |
472 Years (SN 29500 standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
468 Years (SN 29500 standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
472 Years (SN 29500 standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
Degree of pollution |
2 |
Overvoltage category |
II |
Conformance |
CE-compliant |
ATEX |
X II 3 G Ex nA nC IIC T4 Gc X (Please follow the special installation instructions in the documentation!) |
UL, USA |
UL 60079-0 Ed. 6 / UL 60079-15 Ed. 4 |
UL, USA/Canada |
Class I, Zone 2, AEx nA IIC T4, Ex nA IIC Gc X T4 / Class I, Div. 2, Groups A, B, C, D |
UL, Canada |
CSA 22.2 No. 60079-0 Ed. 3 / CSA 22.2 No. 60079-15:16 |
Standards and Regulations |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Type of test |
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 |
Test result |
10 Hz ... 57 Hz, amplitude ±3.5 mm, 57 Hz ... 150 Hz, 5g |
Type of test |
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 |
Test result |
30g for 11 ms, three shocks in each spatial direction |
Type of test |
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 |
Test result |
10g for 16 ms, 1000 shocks in each spatial direction |
Standards/regulations |
EN 61000-4-2 |
Contact discharge |
± 6 kV (Test Level 3) |
Indirect discharge |
± 6 kV |
Standards/regulations |
EN 61000-4-3 |
Frequency range |
80 MHz ... 3 GHz (Test Level 3) |
Standards/regulations |
EN 61000-4-4 |
Comments |
Criterion B |
Standards/regulations |
EN 61000-4-5 |
Signal |
± 1 kV (Data line, asymmetrical) |
Standards/regulations |
EN 61000-6-4 / EN 61000-4-6 |
Frequency range |
0.15 MHz ... 80 MHz |
Standards/regulations |
DIN EN 61643-21 |
Rated insulation voltage |
85 V DC |
IEC test classification |
C2 |
Conformance |
CE-compliant |
ATEX |
X II 3 G Ex nA nC IIC T4 Gc X |
UL, USA |
UL 60079-0 Ed. 6 / UL 60079-15 Ed. 4 |
UL, USA/Canada |
Class I, Zone 2, AEx nA IIC T4, Ex nA IIC Gc X T4 / Class I, Div. 2, Groups A, B, C, D |
UL, Canada |
CSA 22.2 No. 60079-0 Ed. 3 / CSA 22.2 No. 60079-15:16 |
Noxious gas test |
ISA-S71.04-1985 G3 Harsh Group A |